Refurbishment:
Unventilated roof insulation
|
Introduction
• The concept of an ‘unventilated’
roofing is relatively new. Developed over the last two decades, the
principle is based upon the introduction of low vapour resistance (LR),
‘breathable’ sarking membranes to the market. A ‘breather’
membrane allows internally produced water vapour to pass through the
membrane, whilst preventing the ingress of rain and snow.
• Moisture passing through the breather membrane is dispersed
through the ventilated cavity formed by counter battens over the rafters.
• A breather membrane for pitched roofing is defined by BS 5250:2002
as a one that has a water vapour resistance figure of less than 0.25
MNs/g.
• For designers, the advantage of using ‘unventilated’
construction comes from removing the necessity to provide a ventilated
cavity below the sarking. Together with not having to provide a ventilation
pathway, the technique permits insulation to be installed within the
full depth of the rafter.
Breather membrane (in colours) |
U-value target
• The EST target u-value for the rafter-level insulation of a pitched roof is 0.20 W/m2K, though much higher values are achievable.
NB
• The roof insulation methods
illustrated below are for general guidance only. The performance of
products and methods of fixing vary. When specifying, confirm with the
product manufacturer their installation methods and expected performance.
• Beware when combining different insulation materials. Check
with respective manufacturers regarding possible condensation risks.
Insulation positions
The existing (ventilated) roof
|
In addition to the possibility of defective / decaying materials, existing roofs are unlikely to meet with current regulations – even less with best practice standards of thermal performance and air permeability. Check condition of timbers before proceeding.
Between the rafters only
|
The most straightforward treatment is to add insulation
to the full depth of the rafters.
Minimal raising of existing roofline
Maintains internal space and head height.
The shallow depth of the rafters might inhibit achievement of performance
standards.
Thermal bridging through the rafters
Typical U-values: between rafters only
| MIneral wool | U-value W/m2K |
| 150mm | 0.26 |
| PUR / PIR | |
| 150mm | 0.22 |
Between and below rafters with added counter battens
|
By effectively extending the depth of the existing
rafters, it is possible to improve the potential thermal performance
of the roof through providing an extra thickness of insulation.
Minimal raising of existing roof line
Provides for extra depth of insulation.
Reduces internal space and can compromise head height within the room.
Thermal bridging through the rafters
Typical U-values: between and below rafters with added counter battens
| Between (mm) | Below (mm) | U-value W/m2K |
| Mineral wool between and below* | ||
| 100 | 100 | 0.18 |
| 160 | 100 | 0.15 |
| 200 | 100 | 0.12 |
| Sheep's wool | ||
| 100 | ||
Between and below rafters with added rigid insulation
|
By effectively extending the depth of the existing
rafters, it is possible to improve the potential thermal performance
of the roof through providing an extra thickness of insulation.
Minimal raising of existing roof line
Provides for extra depth of insulation.
Reduces internal space and can compromise head height within the room.
Typical U-values: between and below rafters with added rigid insulation
| Between (mm) | Below (mm) | U-value W/m2K |
| Mineral wool between and PUR / PIR below* | ||
| 100 | 40 | 0.23 |
| 160 | 40 | 0.17 |
| 200 | 40 | 0.15 |
| Phenolic foam between and below** | ||
| 75 | 60 | 0.18 |
| 100 | 60 | 0.16 |
| 150 | 60 | 0.12 |
| 200 | 60 | 0.10 |
Between and above rafters
Breathable insulating sarking above rafters
|
Insulation above rafters
|
Adding insulation above the rafters is the ideal solution where internal space is at a premium. Together with insulation between the rafters, this solution can achieve high levels of thermal performance.
In addition to the more common rigid forms of insulation, products new to the UK market have been introduced that combine breathable sarking with insulation. These wood fibre-based boards have been well-proven on the continent since the 1930s. They provide (subject to specification) the potential for a completely ‘breathable’ form of construction by the use of ‘breathable’ insulation materials between the rafters. In a ‘breathing’ roof, VCLs are not required at ceiling level – and only air-tightness membranes are required if using a service void.
Provides for extra depth of insulation
Maintains existing internal space and head heights.
Insulation attached over the rafters reduces thermal bridging
Requires raising of the roof line
Combining an insulation material of vapour resistance over the rafters
(eg foam board) with insulation of relatively low resistance (mineral
wool) between the rafters is not advised unless an effective VCL is
used on the u/s of the rafters.
Typical U-values: between and over rafters
| Between (mm) | Over (mm) | U-value W/m2K |
| Sheep's wool between and over* | ||
| 125 | 50 | 0.24 |
| 150 | 75 | 0.19 |
| 150 | 100 | 0.17 |
| 150 | 175 | 0.14 |
| Hemp / cotton between and insulating wood fibre over** | ||
| 100 | 100 | 0.21 |
| 150 | 100 | 0.17 |
| Mineral wool between and over | ||
| 100 | 70 | 0.23 |
| 125 | 70 | 0.20 |
| 150 | 70 | 0.18 |
| Phenolic foam between and over*** | ||
| 60 | 70 | 0.16 |
| 80 | 90 | 0.13 |
| 100 | 130 | 0.10 |
| Extruded polystyrene (XPS) between and over **** | ||
| 100 | 75 | 0.17 |
| 125 | 75 | 0.15 |
| 150 | 75 | 0.14 |
Air tightness
• In most instances, a combined air tightness
/ vapour control layer (VCL) should be located on the warm side of the
insulation.
• It is essential to maintain the air tightness of the construction.
If services are run behind the air tightness layer, punctures are to
be expected through pipes and wires entering the habitable space. These
punctures should be located through rigorous site inspections and sealed
accordingly.
• An alternative is to form a ‘service zone’ (shown
in these examples) by adding battens to the underside of the VCL before
covering with plasterboard.
General design and installation notes
• Before commencing work, examine the roof
timbers for rot, damp and infestation
• Confirm with the insulation manufacturer the expected u-values
and suitability of planned construction particularly where condensation
control is required.
• Ensure that fire protection is provided to the underside of
the rafters by using 12.5mm plasterboard or similar.
• When using rigid insulation boards, preference should be made
for interlocking boards. All joints should be taped and the joint and
the junction between the rafter and insulation is sealed with foam (leave
a 5mm gap).
• Air cavities where occurring between the vapour control layer
and the u/s of the insulation should be sealed top and bottom.
• Ensure that the space between the wall and roof insulations
is continuous at eaves.
• Avoid recessed lighting
• Cables less than 50mm away from plasterboard should be enclosed
in metal conduits
Downloads
• Practical
refurbishment of solid-walled houses, Energy Saving Trust, 2006
• Energy efficient
refurbishment of existing housing CE83, Energy Saving Trust, 2004
• Refurbishing
dwellings - a summary of best practice CE189, Energy Saving Trust
• Thermal
Improvement of Existing Dwellings, Clarke et al, University
of Strathclyde, 2005
Publications
Building Research Establishment (BRE):
• Thermal Insulation:
Avoiding Risks, C.Stirling, BRE Press, 2001
• Installing Thermal Insulation, BRE Press, 2006
Standards
British Standards Institute (BSI)
• British
Standards associated with insulation (.doc)
Further information
•
Insulation materials compared
•
TRADA
•
National Insulation Association
•
British Urethane Foam Contractors Association
Products and materials
Disclaimer:
GreenSpec accepts no responsibility or liability for any damages or costs
of any type arising out of or in any way connected with your use of this
web site. Data and information is provided for information purposes only,
and is not intended for trading purposes. Neither GreenSpec nor any of
its partners shall be liable for any errors in the content, or for any
actions taken in reliance thereon.











